201
NC2 0 - Manual - 01 - 2015
APPENDIX
201
NC2 0 - Manual - 01 - 2015
APPENDIX
Description Parameter Unit Setting range
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>def within CLP ICLP>def In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 200 step = 1
Inverse time
50/51 First threshold inverse time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>inv within CLP ICLP>inv In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>inv Operating time t>inv s
0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
Phase overcurrent - 50/51 Fundamental
I>> Element
Setpoints
I>> Enable I>> Enable
OFF | ON
ICLP>> Mode ICLP>> Mode
OFF | ON - Element blocking | ON - Change setting
ICLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I>> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I>> Logical block I>>BLK1
OFF | ON
I>> Input selective block I>>BLK2IN
OFF | ON
I>> Output selective block I>>BLK2OUT
OFF | ON
I>> Breaker failure I>>BF
OFF | ON
I>AL Disabling by I>> I>ALdisbyI>>
OFF | ON
I> Disabling by I>> start I>disbyI>>
OFF | ON
I>> Start relays I>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I>> Trip relays I>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I>> Start LEDs I>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I>> Trip LEDs I>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
50/51 Second threshold defi nite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 9.99 step = 0.01
10.0 ... 40.0 step = 0.1
I>>def within CLP ICLP>>def In
0.100 ... 0.999 step = 0.001
1.00 ... 9.99 step = 0.01
10.0 ... 40.0 step = 0.1
I>>def Operating time
Value
s 0.03 ... 10.00 step = 0.01
I>>> Element
Setpoints
I>>> Enable I>>> Enable
OFF | ON
ICLP>>> Mode ICLP>>> Mode
OFF | ON - Element blocking | ON - Change setting
ICLP>>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1