The backlight is the blue light and may be adjusted from fully off, or 1 to fully on at
63.
The contrast may be adjusted from 17 to 37.
6.4 Communications Setup (MODBUS configuration)
1) Press CFG once; screen will change to CONFIG SCREEN
2) On the CONFIG screen, the selections are
Pump Config
System Config
Display Options
Communications
3) Press ↓ until the selection arrows are pointing to the “Communications” option
and then press Selct
4) The CONFIG COMM screen presents the following choices
Modbus Address xxx
Baud Rate 9600
5) Press Exit to get back to the CONFIG SYSTEM screen
6) Press Exit a second time to get back to the normal run screen (or first user-
interface screen, Figure 8)
6.4.2 MODBUS Address
1) Press Selct when the selection arrows are pointing to “Modbus Address” and
adjust the MODBUS address value This should be a unique address on the RS-
485 bus that this controller will respond to. It can range from 1 to 240. For more
information consult with the administrator of the MODBUS / RS-485 system.
2) Press ENTER to lock in (and save) the value
6.4.3 Baud Rate
1) Press ↓ and Selct to adjust the baud rate, baud rate options are:
9600
19200
38400
57600
115200
Note: the 115200 setting should be reserved for very short runs of the RS-485 bus.
Only the 9600 baud option has been thoroughly tested and all other values should
be used with caution.
2) Press Enter to lock in and save the value