51) The RESET ON CONT FAIL selection is either OFF or ON (this setting allows the
next available pump to turn on should the first selected pump trigger a contact fail
alarm, thus generating an error for the first pump and setting it’s HOA status to
OFF)
52) Use the ↑ or ↓ keys to move the selection arrows to the selection of choice and
press Selct
53) Press Next to lock in the value and proceed to RESET CONT FAIL HOA screen
54) The RESET CONT FAIL HOA screen is also an OFF/ON selection (this setting
will allow the controller to automatically set any pump’s HOA status to Auto
should the contact fail alarm be remedied)
55) Use the ↑ or ↓ keys to move the selection arrows to the selection of choice and
press Selct
56) Press Next to lock in the value and proceed to the DELAY BETWEEN PUMPS
setting
57) The DELAY BETWEEN PUMPS setting presents the following: (this is the
amount of time that must pass before another pump can be activated, or
deactivated, to prevent large in-rush currents)
On Delay (sec) xx.x (default 2.0)
Off Delay (sec) xx.x (default 0.0)
58) Use the ↑ or ↓ keys to move the selection arrows to the selection of choice and
press Selct
59) Use the + and keys to adjust the value from 0.0 to 10.0
60) Press Enter to lock in the value
61) Repeat steps 54 to 56 to set both ON and OFF delay times.
62) Press Next to finishe the pump configuration menu and return to the CONFIG
screen
6.2 System Configuration
63) Press CFG once; the screen will change to the CONFIG screen
64) On the CONFIG screen the selections are:
Pump Config
System Config
Display Options
Communications
65) Press ↓ until the selection arrows are pointing to the “System Config” option and
then press Selct
66) The CONFIG SYSTEM menu will present more choices
Time/Date
Password OFF (or ON if previously enabled)
Reset Run Times
Version Number
Clear Log