9.2 Coils
Read: 0x01
Write: 0x05
Format: 0xxxx
Address
Notes
Bit
R/W
0
Local Pump 1 Relay
0
R/O
Local Pump 2 Relay
1
R/O
Local Pump 3 Relay
2
R/O
Local Hi Level Relay
3
R/O
-Not Used-
4-7
R/O
1
Password Enabled
0
R/W
Contact Fail Reset HOA
1
R/W
On Demand Option
2
R/W
Auto Reset Option
3
R/W
Pump Up/Down Option
4
R/W
Float Err Check Opt
5
R/W
Xdcr Fail to Floats
6
R/W
Level Mode Floats
7
R/W
2
AlarmFloat
0
R/W
Pump Active 1
1
R/W
Pump Active 2
2
R/W
-Not Used-
3
-NA-
-Not Used-
4
-NA-
-Not Used-
5
-NA-
-Not Used-
6
-NA-
-Not Used-
7
-NA-
-Not Used-
8
-NA-