7 Appendix
7.1 Fault Table
LED Group of faults Behaviour Cause Trouble shooting
1 Lock • Doordoesnotlock.
• Doordoesnotunlock
and stays closed.
• Locklatchstuckorde-
fective.
• Movelocklatchmanu-
ally. Free manual disen-
gagement by turning
button ccw for about
90°.
• Ifnosuccess,orfault
occurs repeatedly call
TORMAX service.
2 Interface RS232
to user interface
• Operatingmodecan-
not be changed.
• Nodisplayontheuser
interface.
• Connectionfromthe
control unit to the user
interface interrupted
• CallTORMAXservice.
3 Safety facility • Doorremainsopen
or
• Doorstopsattheob-
stacle and leaves can
be moved freely.
• Safetysensorhas
been active for more
than 5 min, or safety
test is negative.
• Reversinghasbeen
triggered 5 times in a
row.
• Removeobjectsinthe
door passage.
• Ifnosuccess,orfault
occurs repeatedly call
TORMAX service.
4 Activators • Doorremainsopen. • Activatorinside/out-
side or key switch has
been active for more
than 5 min.
• Resetkeyswitch.
• Ifnosuccess,orfault
occurs repeatedly call
TORMAX service.
5 System • Doorstopsandleaves
can be moved freely.
• Internalsystemfault. • Changeoperating
mode (= RESET).
• Activatekeyswitch
briey.
• Ifnosuccess,orfault
occurs repeatedly call
TORMAX service.
All No fault • Doorstopsandleaves
can be moved freely.
• Operatingmode
MANUAL
• Changeoperatingmode
No dis-
play
• Noreactionofthe
door and leaves can
be moved freely.
• Mainssupplyinterrupt-
ed.
• Emergencypowersup-
ply switched off.
• Driveisoverheated.
• Switchonmains
➞ main fuse
• Waitfor15min.tilldrive
has cooled down.
• Ifnosuccess,call
TORMAX service.