than the low spare temperature set point in the “Spare temperature” sensor page.
- Alternate Isolating Switch Tripped/Opened**: Activates when the AIS is either tripped or opened. This alarm
condition rings the bell and cannot be silenced.
- Alternate CB Tripped/Opened**: Activates when the ACB is either tripped or opened. This alarm condition rings
the bell and cannot be silenced.
- Water Reservoir Low: Activates if the “Water Reservoir Low” contact input is triggered or if the analog readout of
the water reservoir is enabled and is lower than the water reservoir low set point in the “Water Level” sensor page.
- Water Reservoir Empty: Activates if an external contact triggers the optional “Water Reservoir Empty input.
- High Water Level: Activates if the optional “High Water Level” contact input is triggered or if the analog readout of
the water level is enabled and goes higher than the “High Water Level” set point in the “Water Level” sensor page.
- Main Relief Valve Open: Activates if an external contact triggers the optional “Main Relief Valve Open” input.
- Io_expX-inX alarm: Activates if the specific expansion programmable input on the specific expansion board is
activated and triggered.
- High Motor Temperature: Activates when the optional high motor temperature contact is activated.
- High Motor Vibration: Activates when the optional high motor vibration contact is activated.
- Low ambient temperature: Activates when the ambient temperature is below the factory set value (5 Celsius).
- High ambient temperature: Activates when the ambient temperature is above the factory set value (40 Celsius).
- Control Voltage Not Healthy: Activates when the 24VAC power input to the IO cards is below the acceptable
functional range.
- Soft Starter Fault: Activates when a solid state starter is in fault (for GPS models only).
- Motor Trouble: Activates when a motor related alarm condition is present (overcurrent, undercurrent, fail to start or
ground fault).
- Pump Room Alarm: Activates when a pump room related alarm condition is present (overvoltage, undervoltage,
phase unbalanced).
- Flow Meter On: Activates when the optional flow meter input is activated.
- IO Electric Communication Error: Activates if no communication with the electric IO card could be established for
15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1 minute, the controller
will reboot to try to fix the problem.
- IO Transfer Switch Communication Error**: Activates if no communication with the transfer switch IO card could
be established for 15 seconds. This alarm is critical and triggers the bell. If this alarm persists for more than 1
minute, the controller will reboot to try to fix the problem.
- IO Expansion Communication Error: Activates if no communication with the Expansion IO card could be
established for 15 seconds.
- Communication System Failure: Activates when the communication task has stopped responding. This alarm
condition is critical and the controller will reboot to try to fix the problem.
- File System Failure: Activates when a file system error was detected. This alarm condition is critical and the
controller will reboot to try to fix the problem.