Factory Settings
Config > Advanced > TS Factory Settings
The factory settings are always pre-configured at the factory and set the main parameters of the controller. Most of
the settings found on this page can only be changed by an authorized Tornatech employee and is protected by a
level 8 password.
Normal Dropout Voltage: Percentage of nominal voltage under which the normal power source will be disqualified
(after expiration of the normal outage delay).
Normal pickup voltage: Percentage of nominal voltage above which the normal power source will be re-qualified
(after expiration of the retransfer time - see page 67).
Normal outage: Delay after which the normal power can be disqualified only if the voltage has been all the time
during this delay below the Normal Dropout Voltage.
Alternate dropout voltage: Percentage of nominal voltage under which the alternate power source will be
disqualified.
Alternate pickup voltage: Percentage of alternate voltage above which the normal power source will be qualified
(after expiration of the alternate available delay).
Alternate available delay: Delay after which the alternate power source can be qualified.