104 P9 ASD Installation and Operation Manual
V/f 5-Point Setting Voltage 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 2 establishes the output voltage level that is to
be associated with the frequency setting of
F192 (V/f 5-Point Setting
Frequency 2).
The F701 setting will determine if the selection for this parameter appears in
the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number — F193
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 3 sets the frequency to be associated with
the voltage setting of
F195 (V/f 5-Point Setting Voltage 3).
See F190 and F191 for additional information on this parameter.
Direct Access Number — F194
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
V/f 5-Point Setting Voltage 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 3 establishes the output voltage level that is to
be associated with the frequency setting of
F194 (V/f 5-Point Setting
Frequency 3).
The F701 setting will determine if the selection for this parameter appears in
the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number — F195
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
V/f 5-Point Setting Frequency 4
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 4 sets the frequency to be associated with
the voltage setting of
F197 (V/f 5-Point Setting Voltage 4).
See F190 and F191 for additional information on this parameter.
Direct Access Number — F196
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
V/f 5-Point Setting Voltage 4
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 4 establishes the output voltage level that is to
be associated with the frequency setting of
F196 (V/f 5-Point Setting
Frequency 4).
The F701 setting will determine if the selection for this parameter appears in
the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See F190 and F191 for additional information on this parameter.
Direct Access Number — F197
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
F193 F197