EasyManua.ls Logo

Toshiba P9 - Page 118

Toshiba P9
306 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108 P9 ASD Installation and Operation Manual
V/I Input Point 1 Rate
Program Torque Setpoints
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Torque
Control mode.
V/I Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control
input at the V/I input terminal:
•Set SW301 of the Terminal Board to Voltage or Current (see Figure 9 on
pg. 24).
•Program Fundamental Standard Mode Selection Frequency Mode 1
V/I.
•Program Fundamental Standard Mode Selection Command Mode
Selection Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control
from the V/I input terminal:
•Set V/I Input Point 1 Rate (F205).
•Set V/I Input Point 1 Setting (F201) — the input analog signal level that
corresponds to the torque setting at V/I Input Point 1 Rate.
•Set V/I Input Point 2 Rate (F206).
•Set V/I Input Point 2 Setting (F203) — the input analog signal level that
corresponds to the torque setting at V/I Input Point 2 Rate.
•Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
Once set, as the V/I input voltage changes or the V/I current changes, the
output torque of the ASD will vary in accordance with the above settings.
This parameter sets V/I Input Point 1 Rate and is the output torque value that
is associated with the setting of V/I Input Point 1 Setting when operating in
the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
Note: When using the isolated V/I input terminal, the IICC terminal
must be used as the return (negative) connection.
Direct Access Number — F205
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Torque Settings
F205 F205

Table of Contents

Related product manuals