136 P9 ASD Installation and Operation Manual
Retry Selection
Program Protection Retry/Restart
After a trip has occurred, this parameter sets the number of times that an 
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will NOT initiate the automatic Retry/Restart 
function:
• Input Phase Loss (Input Phase Failure)
• Output Phase Loss (Output Phase Failure)
• Output Current Protection Fault
• Output Current Detector Error
• Load Side Over-Current at Start
• Earth Fault (Ground Fault)
• Over-Current During Acceleration
• Arm Over-Current at Start-Up
• DBR Resistor Over-Current
• Low-Current
• Voltage Drop In Main Circuit
• EEPROM Data Fault (EEPROM Fault)
• Flash Memory/Gate Array/RAM-ROM Fault
•CPU Fault
• Emergency Off (EMG)
• Communication Error
• Option Fault
• Sink/Source Setting Error
• Over-Speed Error
•Over-Torque
• Key Error
• External Thermal Error
• Externally-Controlled Interrupt
See the section titled System Setup Requirements on pg. 8 for additional 
information on this parameter.
Direct Access Number —  F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 0
Maximum — 10
F303 F303