164 P9 ASD Installation and Operation Manual
Time-Based Alternation Process Hold Mode Response Time
Program Virtual Linear Pump Time-Based Alternation
During Time-Based Alternation operation, while running in the Process Hold
mode, this parameter sets the time that the system may operate within the
maximum or minimum Virtual Linear Pump zones before turning the ASD on
or off, respectively.
Direct Access Number — F438
Parameter Type — Numerical
Factory Default — 7.5
Changeable During Run — No
Minimum — 0.0
Maximum — 6553.5
Units — Seconds
Time-Based Alternation Direct Mode Response Time
Program Virtual Linear Pump Time-Based Alternation
During Time-Based Alternation operation, while running in the Direct mode,
this parameter sets the time that the system may operate within the maximum or
minimum Virtual Linear Pump zones before turning the ASD on or off,
respectively.
Direct Access Number — F439
Parameter Type — Numerical
Factory Default — 1000
Changeable During Run — No
Minimum — 0
Maximum — 65535
Units — Seconds
Power Running Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting.
If Setting is selected, the value set at F441 is used as the Power Running
Torque Limit 1 input.
Settings:
1 — V/I
2 — RR
3 — RX
4 — F441 (Setting)
Direct Access Number — F440
Parameter Type — Selection List
Factory Default —F441 (Setting)
Changeable During Run — Yes
Power Running Torque Limit 1 Level
Program Torque Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit 1
setting if the F441 setting is selected at parameter
F440.
This value provides the positive torque upper-limit for the 1 motor.
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal.
If Setting is selected, the value set at F443 is used for this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
4 — F443 (Setting)
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — F443 Setting
Changeable During Run — Yes
F438 F442