206 P9 ASD Installation and Operation Manual
MON2 Terminal Adjustment
Program Ter mi nal Analog Output Terminals
This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of
F674.
See F674 for additional information on this parameter.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
FP Terminal Assignment
Program Ter mi nal Analog Output Terminals
This parameter sets the functionality of the FP output terminal to any one of the
user-selectable functions listed in
Table 7 on pg. 249.
As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note: The duty cycle of the output pulse train remains at 65 ±5.0 µS.
This parameter is used in conjunction with F677.
Direct Access Number — F676
Parameter Type — Selection List
Factory Default Output Frequency
Changeable During Run — Yes
FP Terminal Frequency
Program Ter mi nal Analog Output Terminals
This parameter scales the FP output terminal by setting the pulses-per-second
output signal of the FP terminal.
See F676 for additional information on this parameter.
Direct Access Number — F677
Parameter Type — Numerical
Factory Default 3.84
Changeable During Run — Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
FM Voltage/Current Output Switching
Program Ter mi nal Analog Output Terminals
This parameter is used to select the type of output signal provided at the FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See F005 for additional information on this parameter.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
Direct Access Number — F681
Parameter Type — Selection List
Factory Default 0–10V
Changeable During Run — No
FM Output Gradient Characteristic
Program Ter mi nal Analog Output Terminals
This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See F005 for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F682
Parameter Type — Selection List
Factory Default Plus
Changeable During Run — Yes
FP
F675 F682