78 P9 ASD Installation and Operation Manual
Command Mode Selection
Program Fundamental Standard Mode Selection
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc. The Override
feature may supersede the Command Mode Selection setting (see Command
Mode and Frequency Mode Control on pg. 38).
Settings:
0 — Terminal Block
2 — EOI (Keypad)
3 — RS485
4 — Communication Option Board
Direct Access Number — F003
Parameter Type — Selection List
Factory Default Terminal Block
Changeable During Run — No
Frequency Mode 1
Program Fundamental Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the frequency-control
input for the ASD. The Frequency Mode 2 setting or the Override feature may
supersede the Frequency Mode 1 setting.
Note: Only Bolded items from the Settings list below may be placed in
the Override Mode. See the section titled
Command Mode and
Frequency Mode Control on pg. 38 for additional information on
the Override feature.
Settings:
1 — V/I
2 — RR
3 — RX
5 — EOI (Keypad)
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
Direct Access Number — F004
Parameter Type — Selection List
Factory Default RR
Changeable During Run — No
F003 F004