80 P9 ASD Installation and Operation Manual
Type Reset
Program Utilities
This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a Type Reset results in
one of the following user-selected post-Reset configurations.
Settings:
0 — None
1 — 50 Hz Setting
2 — 60 Hz Setting
3 — Reset to Factory Settings
4 — Clear Past Trips
5 — Clear Run Timer
6 — Initialize Typeform
7 — *Save User Settings
8 — Restore User Settings
9 — Clear Cumulative Fan Timer
10 — Accel/Decel Time Setting 0.01 – 600.00 Seconds
11 — Accel/Decel Time Setting 0.1 – 6000.0 Seconds
12 — Set EOI Memory to Default
Note: User settings that are stored in the memory of the EOI are not
saved via the Save User Settings selection. The unsaved
functions include the EOI Option Setups, (Utilities
Display Parameters, and (Monitor Setup ) Scrolling
Monitor Select.
Direct Access Number — F007
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
Forward/Reverse Run Selection
Program Fundamental Standard Mode Selection
While operating in the Hand mode, this parameter sets the direction of motor
rotation.
From the Frequency Command screen, press the ESC key. At the subsequent
EOI Command screen, select the Direction field and change the setting. Press
the Rotary Encoder and the new setting will be in effect.
This setting will not override parameter F311 (Forward/Reverse Disable).
If either direction is disabled via parameter F311, the disabled direction will not
be recognized if commanded by the keypad. If both directions are disabled via
parameter
F311, the direction command from the keypad will determine the
direction of the motor rotation.
Settings:
0 — Forward
1 — Reverse
2 — Forward (EOI-Switchable F/R)
3 — Reverse (EOI-Switchable F/R)
Direct Access Number — F008
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
F007 F008