T1/T1S User’s Manual
7. Instructions
FUN 036
-
C Subtraction with carry
Expression
Input
-
[
A
-
C
B
®
C
]
-
Output
Function
When the input is ON, the data of
B
and the carry flag (CF = S050) are subtracted from
A
, and the
result is stored in
C
. If borrow is occurred in the operation, the carry flag is set to ON. If the result is
greater than 32767 or smaller than -32768, the output is turned ON.
This instruction is used to perform unsigned subtraction or double-length subtraction.
Execution condition
Input Operation Output CF
OFF No execution OFF
-
ON Execution Normal No borrow OFF Reset
Borrow occurred OFF Set
Overflow / No borrow ON Reset
underflow Borrow occurred ON Set
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Minuend
ÖÖÖÖÖÖÖÖÖÖ Ö Ö
B
Subtrahend
ÖÖÖÖÖÖÖÖÖÖ Ö Ö
C
Difference
ÖÖÖÖÖÖÖÖÖ Ö
Example
When R013 is ON, the data of double-length register RW23
×
RW22 is subtracted from the data of
D0201
×
D0200, and the result is stored in D0211
×
D0210. The RSTC is a instruction to reset the
carry flag before starting the calculation.
If the data of D0201
×
D0200 is 12345678 and RW23
×
RW22 is 12340000, the result 5678 is stored
in D0211
×
D0210.
D0201
×
D0200 12345678
-
D0211
×
D0210 5678
RW23
×
RW22 12340000