1. System Configuration
1.8 Real-time data link system
TOSLINE-F10
TOSLINE-F10 is a high speed data transmission system suited for small points I/O
distribution system. By inserting the TOSLINE-F10 remote card (FR112) into the T1-
40/T1-40S, the T1-40/T1-40S can work as a remote station of the TOSLINE-F10
network. On this network, the T1-40/T1-40S sends 1 word data to the master station
and receives 1 word data from the master station.
Item TOSLINE-F10 system specifications
High speed mode Long distance mode
Topology Bus (terminated at both ends)
Transmission distance
(without repeater)
500 m max. (total) 1 km max. (total)
Transmission speed 750 kbps 250 kbps
Scan transmission
capacity
512 points (32 words) max.
Scan cycle 7 ms/32 words 12 ms/32 words
Error checking CRC check
Typical data link configuration
The figure below shows the typical data link configuration.
NOTE
T2E
(master)
T2E
(remote)
Master
computer
RI/ORI/OT1-40
(
S
)
TOSLINE-F10
RI/O: remote I/O
Operator interface units
T1-40
(
S
)
T1-40
(
S
)
(1) Refer to the separate “T1 User’s Manual
-
Option Card and I/O
Module
-
“ for details of the TOSLINE-F10 remote card (FR112).
(2) Refer to the separate TOSLINE-F10 User’s Manual for details of overall
TOSLINE-F10 system.