88 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Input Terminal 3 (ST) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the ST
(Standby) discrete input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable ST terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F113
Parameter Type — Selection List
Factory Default — Standby
Changeable During Run — No
Input Terminal 4 (RES) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the RES dis-
crete input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable RES terminal to one of
the user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F114
Parameter Type — Selection List
Factory Default — Reset
Changeable During Run — No
Input Terminal 5 (S1) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the S1 discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable S1 terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F115
Parameter Type — Selection List
Factory Default — Fire Speed
Changeable During Run — No
Input Terminal 6 (S2) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the S2 discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable S2 terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F116
Parameter Type — Selection List
Factory Default — Preset Speed
2
Changeable During Run — No
Standby
F113F117