Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 87
Optional V/I Terminal Voltage/Current Selection
Program Frequency V/I Settings
This parameter is used to set the AI2 input terminal to receive
either current or voltage as a control signal.
Note: The Expansion IO Card Option 2 option board (P/N
ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N
58686) for additional information on the function of this terminal.
Settings:
0 — Voltage Input
1 — Current Input
Direct Access Number
F109
Parameter Type — Selection List
Factory Default — Voltage Input
Changeable During Run — No
Always ON Terminal Function 1
Program Terminal Input Terminals
This parameter is used to set the functionality of the virtual dis-
crete input terminal ON. As a virtual terminal, the ON control ter-
minal exists only in memory and is considered always to be in its
True (connected to CC) state.
It is often practical to assign a function to this terminal that the
user desires to be maintained regardless of external conditions or
operations.
This parameter sets the programmable ON terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F110
Parameter Type — Selection List
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Input Terminal 1 (F) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the F discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable F terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F111
Parameter Type — Selection List
Factory Default—Forward
Forward
Changeable During Run — No
Input Terminal 2 (R) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the R discrete
input terminal.
In addition, this input terminal must be specified as Normally
Open or Normally Closed.
This parameter sets the programmable R terminal to one of the
user-selectable functions listed in Table 9 on page 252.
Direct Access Number
F112
Parameter Type — Selection List
Factory Default — Reverse
Changeable During Run — No
F109F113