Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 107
V/I Input Point 2 Rate
Program Torque Setpoints
This parameter is used to set the gain and bias of the V/I input
terminal when the V/I terminal is used as the control input while
operating in the Torque Control mode.
Torque Control is accomplished by establishing an associated V/f
output pattern for a given V/I input level.
This parameter sets V/I Input Point 2 Rate and is the output
torque value that is associated with the setting of V/I Input Point 2
Setting when operating in the Torque Control mode.
This value is entered as 0% to 250% of the rated torque.
See V/I Input Point 1 Rate (F205) for additional information on
this parameter.
Direct Access Number
F206
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Frequency Mode 2
Program Fundamental Standard Mode Selection
This parameter is used to set the source of the frequency com-
mand signal to be used as Frequency Mode 2 in the event that
Frequency Mode 1 is disabled or if Frequency Mode 2 is set up
as the primary control parameter.
See F004 and F200 for additional information on this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
5 — EOI Keypad
6 — RS485/BACnet
7 — Communication Option Board
8 — RX2 (AI1 Option)
9 — Option V/I (AI2 Option)
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
Direct Access Number
F207
Parameter Type — Selection List
Factory Default — V/I
Changeable During Run — No
Frequency Mode Priority Switching Frequency
Program Fundamental Standard Mode Selection
This parameter establishes a threshold frequency that will be
used as a reference when determining when to switch the output
frequency control source from the Frequency Mode 1 setting to
the Frequency Mode 2 setting.
See F200 for additional information on this parameter.
Direct Access Number
F208
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — (ASD-Dependent)
Maximum Maximum Freq.
(F011)
Units — Hz
F206F209