Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 147
PID Feedback Integral (I) Gain
Program Feedback Feedback Settings
This parameter determines the degree that the Integral function
affects the output signal. The smaller the value here, the more
pronounced the effect of the integral function on the output sig-
nal.
Direct Access Number
F363
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.00
PID Deviation Upper Limit
Program Feedback Feedback Settings
This parameter determines the maximum amount that the feed-
back may increase the output signal.
Direct Access Number
F364
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
PID Deviation Lower Limit
Program Feedback Feedback Settings
This parameter determines the maximum amount that the feed-
back may decrease the output signal.
Direct Access Number
F365
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
PID Feedback Differential (D) Gain
Program Feedback Feedback Settings
This parameter determines the degree that the Differential func-
tion affects the output signal. The larger the value entered here,
the more pronounced the affect of the differential function for a
given feedback signal level.
Direct Access Number
F366
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.55
Process Upper Limit
Program Feedback Feedback Settings
Selecting Process PID at parameter F359 allows for this parame-
ter setting to function as the Upper Limit while operating in the
PID Control mode.
Direct Access Number
F367
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
F363F368