148 https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Process Lower Limit
Program Feedback Feedback Settings
Selecting Process PID at parameter F359 allows for this parame-
ter setting to function as the Lower Limit while operating in the
PID Control mode.
Direct Access Number —
F368
Parameter Type — Numerical
Factory Default — Lower-Limit
Freq. (F013)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
PID Control Delay Time
Program Feedback Feedback Settings
This parameter is used to delay the start of PID control at start
up. During the wait time set here, the ASD will follow the fre-
quency control input of the process value and the feedback input
will be ignored. When this setting times out, the PID setup
assumes control.
Direct Access Number —
F369
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 2400
Units — Seconds
PID Output Upper Limit
Program Feedback Feedback Settings
Selecting Speed PID at parameter F359 allows for this parame-
ter setting to function as the Upper Limit while operating in the
PID Control mode.
Direct Access Number —
F370
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
PID Output Lower Limit
Program Feedback Feedback Settings
Selecting Speed PID at parameter F359 allows for this parame-
ter setting to function as the Lower Limit while operating in the
PID Control mode.
Direct Access Number —
F371
Parameter Type — Numerical
Factory Default — Lower-Limit
Freq. (F013)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
F368 – F372