Point 1 Frequency
Program Communications Communication Adjustments
This parameter is used to set the gain and bias of the Communi-
cations Reference speed control input.
See F811 for additional information on this parameter.
This parameter sets Communications Reference Speed Setpoint
1.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Direct Access Number —
F812
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Point 2 Setting
Program Communications Communication Adjustments
This parameter is used to set the gain and bias of the Communi-
cations Reference speed control input.
See F811 for additional information on this parameter.
This parameter sets the Communications Reference input value
that represents Communications Reference Speed Setpoint 2
(frequency). This value is entered as 0 to 100% of the Communi-
cations Reference input value range.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Direct Access Number —
F813
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Point 2 Frequency
Program Communications Communication Adjustments
This parameter is used to set the gain and bias of the Communi-
cations Reference speed control input.
See F811 for additional information on this parameter.
This parameter sets the Communications Reference Speed Set-
point 2.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Direct Access Number —
F814
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Address Monitor (Modbus+)
Program Communications Modbus Settings
This parameter is used to select a node/station to monitor.
Direct Access Number —
F815
Parameter Type — Numerical
Factory Default — 1
Changeable During Run — Yes
Minimum — 1
Maximum — 64
F812 – F816