Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 219
Command Selection (Modbus+)
Program Communications Modbus Settings
This parameter sets the command function to Prohibit or
Permit.
Settings:
0 — Prohibit
1 — Permit
Direct Access Number
F816
Parameter Type — Selection List
Factory Default — Prohibit
Changeable During Run — Yes
Number of Command (Modbus+)
Program Communications Modbus Settings
This parameter is used to assign commands.
Settings:
0 — Prohibit
1 — Permit
Direct Access Number
F817
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 8
Number of Monitors (Modbus+)
Program Communications Modbus Settings
This parameter is used to assign monitors.
Direct Access Number
F818
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 8
Command Station (Modbus+)
Program Communications Modbus Settings
This parameter is used to assign the command station.
Direct Access Number
F819
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 64
Baud Rate (4-Wire RS485)
Program Communications Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number
F820
Parameter Type — Selection List
Factory Default — 19200
Changeable During Run — Yes
F816F821