Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 247
Monitor Output Function Command 41
Program My Function My Function Monitor
This parameter plays a role in the setup of the My Function fea-
ture by allowing the user to select the Maximum, Minimum, or
Normal (Avg.) value of the parameter F971 selection to be
recorded and output as a monitored function.
Settings:
0 — Normal
1 — Maximum
2 — Minimum
See the My Function Instruction Manual (P/N E6581335) for a
complete description of the setup requirements and operational
information of the Monitor Output Function parameter.
Direct Access Number
F972
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
Virtual Input Terminal Selection 1
Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input
Terminal 1. As a virtual terminal, it exists only in memory and is
considered always to be in its True (connected to CC) state.
It is often practical to assign a function to this terminal that the
user desires to be maintained regardless of external conditions or
operations.
This parameter sets the programmable Virtual Input Terminal 1
terminal to one of the functions that are listed in Table 9 on
page 252.
In addition, the input terminal must be specified as Normally
Open or Normally Closed.
Direct Access Number
F973
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Virtual Input Terminal Selection 2
Program Terminal Input Terminals
This parameter is used to set the functionality of the Virtual Input
Terminal 2. As a virtual terminal, it exists only in memory and is
considered always to be in its True (connected to CC) state.
It is often practical to assign a function to this terminal that the
user desires to be maintained regardless of external conditions or
operations.
This parameter sets the programmable Virtual Input Terminal 2
terminal to one of the functions that are listed in Table 9 on
page 252.
In addition, the input terminal must be specified as Normally
Open or Normally Closed.
Direct Access Number
F974
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
F972F975