Common Configurable Control Options
*Accessed via Toshiba hard wired remote controller RBC-AMS51E-ES
Relocation of room temperature sensing from return air to remote controller sensor
1) Press the button to
display the Menu screen
2) Press and hold the button
and the “button at the same time
for more than 4 seconds to display the
Field setting menu
3) Scroll down to item “5” using the
“button.
4) Press “F2” Code (DN) 10
will be highlighted on the left of the display.
5) Scroll the Code (DN) to 32 using the
“buttons.
6) When Code (DN) 32 is highlighted on the left
press “ [F2]” to highlight “Data
on the right.
7) Change “Data” from “0000” to “0001” by
pressing the “
8) Press “ “follow on screen instructions.