EasyManua.ls Logo

Toshiba TOSVERT VF-S15 series - TPDO Object

Toshiba TOSVERT VF-S15 series
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E6581911
- 23 -
5.1.5. TPDO object
Index
(Hex)
Sub
index
Access
Type
Default value
Description
1800
00
R
u8
0x05
Transmit PDO1: Number of entries
01
R/W
u32
0x00000180
+ Node-ID
Transmit PDO1: COB-ID
The default value is 0x00000180 (parameter data c713)
+Node-ID. If set other than 0x00000180 except bit31, new set
data is used for COB-ID(=new data).
Bit31 is an enable/disable flag of TPDO1 data set.
02
R/W
u8
0x0FF
Transmit PDO1: Transmission type:
“asynchronous” (254 or 255), “cyclic synchronous” (0~240).
03
R/W
u16
0x0064
Transmit PDO1: Inhibit time: unit = 100us
Minimum time between two transmissions
04
R/W
u8
0x00
Transmit PDO1: Reserved
05
R/W
u16
0x0000
Transmit PDO1: Event timer: 0=Disable, unit = 1 ms
When Transmission type=254 or 255, this object defines a
transmission frequency for this PDO.
1801
00
R
u8
0x05
Transmit PDO2: Number of entries
01
R/W
u32
0x80000280
+ Node-ID
Transmit PDO2: COB-ID
The default value is 0x80000280 (parameter data c723)
+Node-ID. If set other than 0x80000280 except bit31, new set
data is used for COB-ID(=new data).
Bit31 is an enable/disable flag of TPDO2 data set.
02
R/W
u8
0x0FF
Transmit PDO2 : Transmission type:
“asynchronous” (254 or 255), “cyclic synchronous” (0~240).
03
R/W
u16
0x0064
Transmit PDO2: Inhibit time: unit = 100us
Minimum time between two transmissions
04
R/W
u8
0x00
Transmit PDO2: Reserved
05
R/W
u16
0x0000
Transmit PDO2: Event timer: 0=Disable, unit = 1 ms
When Transmission type=254 or 255, this object defines a
transmission frequency for this PDO.
1802
00
R
u8
0x05
Transmit PDO3: Number of entries
01
R/W
u32
0x80000380
+ Node-ID
Transmit PDO3: COB-ID
The default value is 0x80000380 (parameter data c733)
+Node-ID. If set other than 0x80000380 except bit31, new set
data is used for COB-ID(=new data).
Bit31 is an enable/disable flag of TPDO3 data set.
02
R/W
u8
0x0FF
Transmit PDO3: Transmission type:
“asynchronous” (254 or 255), “cyclic synchronous” (0~240).
03
R/W
u16
0x0064
Transmit PDO3: Inhibit time: unit = 100us
Minimum time between two transmissions
04
R/W
u8
0x00
Transmit PDO3: Reserved
05
R/W
u16
0x0000
Transmit PDO3: Event timer: 0=Disable, unit = 1 ms
When Transmission type=254 or 255, this object defines a
transmission frequency for this PDO.
1814
00
R
u8
0x05
Transmit PDO21: Number of entries
01
R/W
u32
0x80000480
+ Node-ID
Transmit PDO21: COB-ID
The default value is 0x80000480 (parameter data c743)
+Node-ID. If set other than 0x80000480 except bit31, new set
data is used for COB-ID(=new data).
Bit31 is an enable/disable flag of TPDO21 data set.
02
R/W
u8
0x0FF
Transmit PDO21: Transmission type:
“asynchronous” (254 or 255), “cyclic synchronous” (0~240).
03
R/W
u16
0x0064
Transmit PDO21: Inhibit time: unit = 100us
Minimum time between two transmissions
04
R/W
u8
0x00
Transmit PDO21: Reserved
05
R/W
u16
0x0000
Transmit PDO21: Event timer: 0=Disable, unit = 1 ms
When Transmission type=254 or 255, this object defines a
transmission frequency for this PDO.

Table of Contents