piping will prevent condensation from forming on the
pipe and dripping on the floor.
Notes:
Trane does not provide insulation on the
economizing piping package. The insulation
must be field provided and field installed.
Trane does not provide condensate
overflow protection of the waterside
economizer. This must be field provided
and installed.
8. Field pipe the drain lines of the waterside economizer
and water-source heat pump. Both the WSE and unit
condensate drains must be separately trapped for
proper handling of condensation (see Figure 38, p. 41
). Both Vertical and Horizontal units will be piped similar
to each other. The drain connection is located on the
bottom side of the economizing coil.
Figure 38. Step 8
J
L
H
L
J
H
NEGATIVE PRESSURE TRAPPING
H=1" (25.4 mm) FOR EVERY 1"
(25.4 mm) OF MAXIMUM
NEGATIVE STATIC PRESSURE
+1" (25.4 mm).
J= HALF OF H.
L=H+J+ PIPE DIAMETER +INSULATION.
Table 27. Economizer part numbers
Supply-Air
Arrangement
Unit Part Number
Left Supply
EXVG009-012 WSHPECN00016
EXVG015 WSHPECN00017
EXVG018-024,
DXVG024
WSHPECN00018
EXVG030-036,
DXVG036
WSHPECN00019
EXVG042-048,
DXVG048
WSHPECN00020
EXVG060-070,
DXVG060-070
WSHPECN00021
Right Supply
EXVG009-012 WSHPECN00023
EXVG015 WSHPECN00024
EXVG018-024,
DXVG024
WSHPECN00025
EXVG030-036,
DXVG036
WSHPECN00026
EXVG042-048,
DXVG048
WSHPECN00027
EXVG060-070,
DXVG060-070
WSHPECN00028
Waterside Economizer Installation for
Vertical Units
The following steps were sequenced to aid in the
installation and pairing of a water side economizer to a
EXV and DXV water source heat pump.
1. Remove the filter bracket from the unit. It is secured by
five screws: three on top (circled) and two on the
bottom (not shown). Do not discard the filter brackets.