6.4 Non Ducted Applications
Non-Ducted Return Installations:
• Installation in a closet, an alcove, or a utility room
without a return duct requires the use of a plenum
accessory kit as it uses the area space as a return
air plenum. Minimum clearances to combustible
materials and service access must be observed (see
outline drawing).
• This area may also be used for other purposes,
including an electric hot water heater, but in no case
shall a fossil fuel device be installed and/or operated
in the same closet, alcove, or utility room.
• Review local codes to determine limitations if the unit
is installed without a return air duct.
Supply Duct
Plenum
Accessory
with safety guard
HAZARDOUS VAPORS! Do not install an air
handler with a non-ducted return in the same closet,
alcove, or utility room as a fossil fuel device. Hazard-
ous vapors can be distributed throughout the condi-
tioned space and equipment damage can result.
Ducted Return Installations:
• Installation in an attic, garage, or crawl space with
ducted supply and return air is appropriate. Minimum
clearances to combustible materials and service
access must be observed (see outline drawing).
6.5 Ducted Applications
Return Duct
Non-Ducted
Return
Minimum Unit Clearance Table
To Combustible Material
(Required)
Service Clearance
(Recommended)
Sides 0” 2”
Front 0” 21”
Back 0” 0”
Inlet Duct 0” N/A
Outlet Duct 0” N/A
6.3 Minimum Clearance Table
Supply Duct
Ducted Return