EasyManua.ls Logo

Trane GAF2A0A36M31EC - Refrigerant Line; Refrigerant Line Connection Sizes; Refrigerant System Layout Diagram

Trane GAF2A0A36M31EC
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Section 10. Refrigerant Line
10.1 Refrigerant Line Connection Sizes
10.2 Refrigerant System Layout
Refrigerant Line Set and Connection Sizes
Model
Vapor Line
Connection
Liquid Line
Connection
GAFA2A0A36M31SC, GAFA2A0A36M31SC
3/4 3/8
Notes:
1. This table indicates the tubing connection diameters at the indoor coil. A field supplied reduc-
ing coupling may be required.
2. All AHRI listed systems are tested with 25 feet of refrigeration tubing; the rated tubing diam-
eters are located in the electronic performance data system.
3. If the refrigeration lines exceed 60 feet in linear length and / or if alternate size refrigeration
tubing is present at the job, please consult SS-APG006-EN or 32-3312-**(latest version)
Table 10.1
EEV Stepper
Motor
Vapor Line
Liquid Line
Evaporator Temperature
Sensor (ET)
- located on 3/8" Aluminum
distributor tube
(orange wires)
Gas Temperature
Sensor (GT)
- located on copper
section of manifold
(black wires)