Mounting/Locations
These units are suitable for installation on combustible flooring.
Single, double and triple duct furnace only models have base rails which can be mounted either
on solid planking or steel channels. All other units installed on field furnished supports must use
the recommended method shown in Mounting on Field Furnished Supports or equivalent.
Roof curb kits for rooftop units are shipped unassembled. Included with the roof curb kit are
insulated or uninsulated curb rails, bolts and screws needed for assembly, sealant, a roll of self-
adhering rubber gasketing, and installation instructions. Roof insulation, cant stripping, flashing,
roof felts, caulking, and nails must be furnished by the installer. See , separate roof curb
specifications.
If a variable frequency drive (VFD) has been ordered with the unit, consideration should be made
for the VFD operating temperature range: 14°F to 130°F. For temperatures below 14°F, VFD must
be factory-installed within the VFD Enclosure accessory (Model Digit 22, option 9), or field-
mounted indoors.