Remove the shipping hardware from each
compressor assembly.
Remove the shipping hold-down bolts and shipping
channels from the supply and relief /return fans
with rubber or spring isolators.
Check all supply and relief/return fan spring
isolators for proper adjustment.
Verify that all plastic coverings are removed from
the compressors.
Verify all discharge line service valves (one per
circuit) are back seated.
Main Electrical Power
Verify that the power supply complies with the unit
nameplate specifications. Refer to Main Unit Power
Wiring in the Installation chapter.
Inspect all control panel components; tighten any
loose connections.
Connect properly sized and protected power supply
wiring to a field-supplied/installed disconnect and
unit
Properly ground the unit.
All field-installed wiring must comply with NEC and
applicable local codes.
Field Installed Control Wiring
Complete the field wiring connections for the
variable air volume controls as applicable.
NNoottee:: All field-installed wiring must comply with NEC
and applicable local codes.
Electric Heat Units
Verify that the power supply complies with the
electric heater specifications on the unit and heater
nameplate.
Inspect the heater junction box and control panel;
tighten any loose connections.
Check electric heat circuits for continuity.
On SEH_L units with 200V or 230V electric heat
(requires separate power supply to heater)
Connect properly sized and protected power supply
wiring for the electric heat from a dedicated, field-
supplied/installed disconnect to terminal block
3XD5, or to an optional unit-mounted disconnect
switch 3QB4.
Gas Heat (SFH_)
Gas supply line properly sized and connected to the
unit gas train.
All gas piping joints properly sealed.
Drip leg installed in the gas piping near the unit.
Gas piping leak checked with a soap solution. If
piping connections to the unit are complete, do not
pressurize piping in excess of 0.50 psig or 14 inches
w.c. to prevent component failure.
Main supply gas pressure adequate.
Flue Tubes clear of any obstructions.
Factory-supplied flue assembly installed on the
unit.
LP (Propane) kit parts installed (if required).
Connect the 3/4" CPVC furnace drain stubout to a
proper condensate drain. Provide heat tape or
insulation for condensate drain as needed.
Hot Water Heat (SLH_)
Route properly sized water piping through the base
of the unit into the heating section.
Install the factory-supplied, 3-way modulating
valve.
Complete the valve actuator wiring.
Steam Heat (SSH_)
Install an automatic air vent at the top of the return
water coil header.
Route properly sized steam piping through the base
of the unit into the heating section.
Install the factory-supplied, 2-way modulating valve
Complete the valve actuator wiring.
Install 1/2", 15-degree swing-check vacuum breaker
(s) at the top of each coil section. Vent breaker(s) to
the atmosphere or merge with return main at
discharge side of steam trap.
Position the steam trap discharge at least 12" below
the outlet connection on the coil.
Use float and thermostatic traps in the system, as
required by the application.
O/A Pressure Sensor and Tubing
Installation
(All units with Statitrac or return fans)
O/A pressure sensor mounted to the roof bracket.
Factory supplied pneumatic tubing installed
between the O/A pressure sensor and the connector
on the vertical support.
Field supplied pneumatic tubing connected to the
proper fitting on the space pressure transducer
located in the filter section, and the other end
routed to a suitable sensing location within the
controlled space (Statitrac only).
Modulating Reheat (S_H_)
Install space humidity and temperature sensors.
Refer to unit diagrams for guidelines.
IInnssttaallllaattiioonn

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak 1 and is the answer not in the manual?

Trane IntelliPak 1 Specifications

General IconGeneral
BrandTrane
ModelIntelliPak 1
CategoryAir Conditioner
LanguageEnglish

Related product manuals