RT-SVX072A-EN
Table 36. Component static pressure drops (in. W.G.), 90 to 130 tons air-cooled
Nom CFM Std
Evap Coil
High Cap
Evap Heating System
Filters
Std
Roof
Econ
w/ or
w/out
Relief
Dry
Wet
Dry
Wet
SFHL SEHL SLHL SSHL
Throwaway
Perm
Wire
Bag &
Pre
Cart &
Pre
Final
Cart
Low
High
All kW
Low
High
Low
High
Std
High
90
27000 0.40 0.53 0.60 0.80
N/A
0.25 0.13 0.26 0.31 0.22 0.32 0.11 0.13
N/A
0.68 0.65 0.77
N/A
0.20
32000 0.53 0.70 0.80 1.03
N/A
0.31 0.16 0.35 0.41 0.30 0.43 0.14 0.16
N/A
0.84 0.84 1.07
N/A
0.31
37000 0.67 0.88 1.01 1.32
N/A
0.39 0.23 0.45 0.52 0.40 0.55 0.17 0.19
N/A
1.02 1.04 1.43
N/A
0.41
42000 0.83 1.08 1.25 1.62
N/A
0.46 0.29 0.56 0.65 0.50 0.68 0.21 0.22
N/A
1.19 1.06 1.86
N/A
0.52
45000 0.93 1.20 1.40 1.80
N/A
0.52 0.32 0.63 0.73 0.58 0.76 0.24 0.24
N/A N/A N/A
2.14
N/A
0.63
105
31000
N/A N/A
0.63 0.83
N/A
0.28 0.17 0.33 0.39 0.29 0.40
N/A
0.13
N/A
0.82 0.80 1.00
N/A
0.22
35000
N/A N/A
0.77 1.01
N/A
0.36 0.21 0.41 0.48 0.36 0.50
N/A
0.16
N/A
0.96 0.96 1.28
N/A
0.32
39000
N/A N/A
0.92 1.20
N/A
0.42 0.26 0.49 0.57 0.44 0.60
N/A
0.19
N/A
1.09 1.12 1.59
N/A
0.44
43000
N/A N/A
1.08 1.40
N/A
0.45 0.30 0.57 0.66 0.53 0.71
N/A
0.22
N/A
1.22 1.30 1.95
N/A
0.54
46000
N/A N/A
1.21 1.56
N/A
0.55 0.34 0.65 0.75 0.61 0.79
N/A
0.24
N/A N/A N/A
2.24
N/A
0.64
115/
130
31000 0.76 1.00
N/A N/A N/A
0.28 0.17 0.33 0.39 0.29 0.40
N/A
0.13
N/A
0.82 0.80 1.00
N/A
0.22
35000 0.92 1.21
N/A N/A N/A
0.36 0.21 0.41 0.48 0.36 0.50
N/A
0.16
N/A
0.96 0.96 1.28
N/A
0.32
39000 1.10 1.44
N/A N/A N/A
0.42 0.26 0.49 0.57 0.44 0.60
N/A
0.19
N/A
1.09 1.12 1.59
N/A
0.44
43000 1.30 1.68
N/A N/A N/A
0.45 0.30 0.57 0.66 0.53 0.71
N/A
0.22
N/A
1.22 1.30 1.95
N/A
0.54
46000 1.45 1.86
N/A N/A N/A
0.55 0.34 0.65 0.75 0.61 0.79
N/A
0.24
N/A N/A N/A
2.24
N/A
0.64
Notes:
1. Static pressure drops of accessory components must be added to external static pressure to enter fan selection tables.
2. Gas heat section maximum temperature rise of 60° F.
3. Throwaway filter option limited to 300 ft/min face velocity.
4. Bag filter option limited to 740 ft/min face velocity.
5. Horizontal roof curbs assume 0.50" static pressure drop or double the standard roof curb pressure drop, whichever is greater.
6. No additional pressure loss for model SXHL.
7. For final filters w/ prefilters (digit 13 = M, N, P, Q) also add pressure drop for throwaway filter.
UUnniitt SSttaarrttuupp

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak 1 and is the answer not in the manual?

Trane IntelliPak 1 Specifications

General IconGeneral
BrandTrane
ModelIntelliPak 1
CategoryAir Conditioner
LanguageEnglish

Related product manuals