48
System Testing & Troubleshooting
DIAGNOSTIC DISPLAYED REASON FOR DIAGNOSTIC UCM’S REACTION RESET REQUIRED
CGM ICS Temperature Sensor Fail
Problem: CGM is receiving a signal
which is out of range from the CGM
ICS Temperature Sensor input.
The unit is reading a signal that is out of
range for the CGM ICS Temperature
sensor input on the CGM. (Temp < -40 F
or Temp > 200 F).
No change in unit operation
occurs. This diagnostic is for
information only.
(INFO) An automatic reset occurs
after the CGM ICS Temperature
Sensor returns to its allowable
range. In order to prevent rapid
cycling of the diagnostic, there is a
10 second delay prior to the
i
CGM Module Data Storage Error
Problem: There was a data
transmission error.
Check: This can be caused by an
intermittent power loss. Turn the
unit off for 1-2 minutes, then back on
again. If diagnostic persists, then
the CGM ma
y
need to be re
p
laced.
An error occurred while the CGM was
writing data to its internal non-volatile
memory (EEPROM).
An information only diagnostic will
be displayed at the Human
Interface.
(INFO) A manual reset may be
made at the Human Interface, at
Tracer, or by cycling power to the
CGM.
CGM OA Temp Sensor Failure
Problem: The Outside Air
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sensor and CGM.
The unit is reading a signal that is out of
range for the Outside Air Temperature
sensor input on the CGM. (Temp < -40 F
or Temp > 200 F).
Unit actions that occur when this
diagnostic is active include;
a. Low Ambient Compressor
Lockout function is disabled
b. Low Ambient Pump Override
function is activated (ie: Solution
Pump ON request is issued).
c. LPC Bypass Time is set to
Minimum Bypass Time (time used
for OA Temp >65 degF).
d. If Leaving Solution Reset type
selected is OA Temp Reset, then
the Reset type reverts to NONE
for the duration of the failure.
(PAR) An automatic reset occurs
after the OA Temp input returns to
its allowable range. In order to
prevent rapid cycling of the
Diagnostic, there is a 10 second
delay before the automatic reset.
CGM Zone Temp Sensor Failure
Problem: The CGM Zone
Temperature sensor input is out of
range.
Check: Sensor resistance between
830 ohms (200 F) and 345.7Kohms
(-40 F). If so, check field/unit wiring
between Sensor and CGM.
The Leaving Solution Reset type
selected is Zone Temp Reset, and the
unit is reading a signal that is out of
range for this input (Temp < -40 F or
Temp > 200 F).
The Reset type reverts to NONE
for the duration of the failure.
(PAR) An automatic reset occurs
after the designated Zone
Temperature signal returns to its
allowable range. In order to prevent
rapid cycling of the Diagnostic,
there is a 10 second delay before
the automatic reset.