Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BINARY OUTPUTS
Cold Generator External Leaving Solution Setpoint None Emergency Stop Liquid Line Relay (Ckt #1)
Module (CGM) Evap Entering Solution Temp External Auto/Stop Liquid Line Relay (Ckt #2)
Evap Leaving Solution Temp Ice Building Hot Gas Bypass Relay
ICS Defined Temp Flow Proving • Alarm Relay
Condenser Entering Solution Temp Condenser Pump Low Ambient Bypass 1 Relay
Outdoor Air Temp Proving • Low Ambient Bypass 2 Relay
Condenser Leaving Solution Temp Solution Pump Relay
Zone Temperature Ice Making Relay
ICS Temperature ICS Relay
Current Sensing Compressor A, Phase A None None None
Module (CSM) • Compressor A, Phase B
• Compressor B, Phase A
• Compressor B, Phase C
• Compressor C, Phase B
• Compressor C, Phase C
• Compressor D, Phase A
• Compressor D, Phase C
Generic Building Four inputs, which can be assigned: None Demand Limit Five outputs, which can
Automation System 0- Occ Zone Cool Setpoint
be assigned:
5VDC (GBAS 0-5V) Unocc Zone Cool Setpoint Compressors running
Module Occ Zone Heat Setpoint Running at maximum
Unocc Zone Heat Setpoint
capacity
Supply Air Cooling Setpoint Selected diagnostics
Supply Air Heating Setpoint messages
Space Static Pressure Setpoint
• SA Static Pressure Setpoint
Min OA CFM Setpoint
Leaving Solution Setpoint
Ice Build Terminate Setpoint
Hot Start Load Limit Setpoint
Maximum Capacity Level Setpoint