Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BINARY OUTPUTS
Cold Generator • External Leaving Solution Setpoint • None • Emergency Stop • Liquid Line Relay (Ckt #1)
Module (CGM) • Evap Entering Solution Temp • External Auto/Stop • Liquid Line Relay (Ckt #2)
• Evap Leaving Solution Temp • Ice Building • Hot Gas Bypass Relay
• ICS Defined Temp • Flow Proving • Alarm Relay
• Condenser Entering Solution Temp • Condenser Pump • Low Ambient Bypass 1 Relay
• Outdoor Air Temp Proving • Low Ambient Bypass 2 Relay
• Condenser Leaving Solution Temp • Solution Pump Relay
• Zone Temperature • Ice Making Relay
• ICS Temperature • ICS Relay
Current Sensing • Compressor A, Phase A • None • None • None
Module (CSM) • Compressor A, Phase B
• Compressor B, Phase A
• Compressor B, Phase C
• Compressor C, Phase B
• Compressor C, Phase C
• Compressor D, Phase A
• Compressor D, Phase C
Generic Building Four inputs, which can be assigned: • None • Demand Limit Five outputs, which can
Automation System 0- • Occ Zone Cool Setpoint
be assigned:
5VDC (GBAS 0-5V) • Unocc Zone Cool Setpoint • Compressors running
Module • Occ Zone Heat Setpoint • Running at maximum
• Unocc Zone Heat Setpoint
capacity
• Supply Air Cooling Setpoint • Selected diagnostics
• Supply Air Heating Setpoint messages
• Space Static Pressure Setpoint
• SA Static Pressure Setpoint
• Min OA CFM Setpoint
• Leaving Solution Setpoint
• Ice Build Terminate Setpoint
• Hot Start Load Limit Setpoint
• Maximum Capacity Level Setpoint