64
Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BINARY OUTPUTS
Generic Building Four inputs, which can Four outputs, which can • Demand Limit One output, which
Automation System 0-
be assi
ned: can be assi
ned:
10VDC (GBAS 0-10V) • Leaving Solution Setpoint • Leaving Soln Temp • Compressors running
Module • Ice Build Terminate Setpoint • Entering Soln Temp • Running at maximum
• Hot Start Load Limit Setpoint • Sat. Cond Temp Ckt1
capacit
• Maximum Capacity Level • Sat. Cond Temp Ckt2 • Selected diagnostics
Setpoint • Evap Temp Ckt1 messages
• Evap Temp Ckt2
• ICS Defined Temp
• Liquid Pressure Ckt1
• Suction Pressure Ckt1
• Liquid Pressure Ckt2
• Suction Pressure Ckt2
• Active Cooling Capacity
• Outdoor Air Temp
• Saturated Liquid Temp Ckt1
• Saturated Liquid Temp Ckt2
Human Interface (HI) • None • None • None • None
Module
Interprocessor • None • None • None • None
Communications
Bridge (IPCB) Module
Multiple Compressor • Evap/Suction Temperature • Condenser Fan Speed • Compressor Proving (Ckt #1) • Compressor Relay K11
Module (MCM)
(Ckt #1)
(Low Ambient Ckt #1) • Compressor Proving (Ckt #2) • Compressor Relay K12
• Evap/Suction Temperature • Condenser Fan Speed • Low Pressure Cutout(Ckt #1) • Compressor Relay K3
(Ckt #2)
(Low Ambient Ckt #2) • Low Pressure Cutout (Ckt #2) • Compressor Relay K4
• Saturated Condenser • High Pressure Control (Ckt #1) • Condenser Fan 1A
Temperature Sensor (Ckt #1) • High Pressure Control (Ckt #2) • Condenser Fan 1B
• Saturated Condenser • Condenser Fan 1C
Temperature Sensor (Ckt #2) • Condenser Fan 2A
• Saturated Liquid Temp (Ckt #1) • Condenser Fan 2B
• Saturated Liquid Temp (Ckt #2) • Condenser Fan 2C
• Heater Tape
Single Compressor • Evap/Suction Temperature • Condenser Fan Speed • Compressor Proving • Compressor Relay K11
Module (SCM) • Saturated Condenser (Low Ambient) • Low Pressure Cutout • Compressor Relay K12
Temperature
• High Pressure Control • Condenser Fan A
• Saturated Liquid Temperature
• Condenser Fan B