Module I/O Summary
UNIT MODULE ANALOG INPUTS ANALOG OUTPUTS BINARY INPUTS BINARY OUTPUTS
Generic Building Four inputs, which can Four outputs, which can • Demand Limit One output, which
Automation System 0-
be assigned:
be assi
g
ned: can be assi
g
ned:
10VDC (GBAS 0-10V) Leaving Solution Setpoint Leaving Soln Temp • Compressors running
Module • Ice Build Terminate Setpoint Entering Soln Temp Running at maximum
Hot Start Load Limit Setpoint Sat. Cond Temp Ckt1
capacit
y
Maximum Capacity Level Sat. Cond Temp Ckt2 Selected diagnostics
Setpoint Evap Temp Ckt1 messages
• Evap Temp Ckt2
• ICS Defined Temp
• Liquid Pressure Ckt1
• Suction Pressure Ckt1
• Liquid Pressure Ckt2
• Suction Pressure Ckt2
Active Cooling Capacity
Outdoor Air Temp
Saturated Liquid Temp Ckt1
Saturated Liquid Temp Ckt2
Human Interface (HI) None None None None
Module
Interprocessor • None None • None • None
Communications
Bridge (IPCB) Module
Multiple Compressor Evap/Suction Temperature Condenser Fan Speed Compressor Proving (Ckt #1) Compressor Relay K11
Module (MCM)
(Ckt #1)
(Low Ambient Ckt #1) Compressor Proving (Ckt #2) Compressor Relay K12
Evap/Suction Temperature Condenser Fan Speed Low Pressure Cutout(Ckt #1) Compressor Relay K3
(Ckt #2)
(Low Ambient Ckt #2) Low Pressure Cutout (Ckt #2) Compressor Relay K4
Saturated Condenser High Pressure Control (Ckt #1) Condenser Fan 1A
Temperature Sensor (Ckt #1) High Pressure Control (Ckt #2) Condenser Fan 1B
Saturated Condenser Condenser Fan 1C
Temperature Sensor (Ckt #2) Condenser Fan 2A
Saturated Liquid Temp (Ckt #1) Condenser Fan 2B
Saturated Liquid Temp (Ckt #2) Condenser Fan 2C
Heater Tape
Single Compressor • Evap/Suction Temperature Condenser Fan Speed Compressor Proving Compressor Relay K11
Module (SCM) Saturated Condenser (Low Ambient) Low Pressure Cutout Compressor Relay K12
Temperature
High Pressure Control • Condenser Fan A
Saturated Liquid Temperature
Condenser Fan B