RT-SVP04F-EN 45
System Operating Status
Active Morning WU Temp Sensor Input From
RTM ZONE TEMP INPUT is 82.0 F
Used With: All Units when Gas,
Electric, Hydronic or External Heat is
installed and Morning Warmup is
enabled
1. Press the NEXT key until the following screen is displayed.
(if applicable)
Possible Values: RTM Zone Temp
Input, NSB Panel Temp Sensor
Input, RTM Aux Temp Input, Heat
Module Aux Temp Input, ECEM
Return Air Temp Input, BAS/
Network, Sensor range: -40 F to
200 F
Active Space Humidity Sensor Input From Used With: All units with
Humidification option enabled.
Possible Values: RTM Space,
Humidity Input, BAS/Network, ECEM
RA Humidity Input; Range 10-90%
RTM space Humidity Input is 55%
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Space CO
2
Sensor Input From Used With: All units with VCM
installed.
Possible Values: VCM SPACE CO
2
INPUT, BAS/Network; Range 50-
2000 ppm
VCM Space CO
2
Input is 600 ppm
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
Active Dehumid OVRD Temp Input From Used With: All units with
Dehumidification installed.
Possible Values: RTM Zone Temp
input, NSB Panel Temp Sensor input,
RTM Aux Temp input, Heat Module
Aux Temp input, BAS/Network,
ECEM Return Air Temp input;
Range: -40.0 to 200.0 F
RTM ZONE TEMP INPUT is 73.5°F
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)

Table of Contents