66 RT-SVP04F-EN
System Programming SETUP
Ventilation Override Definitions (with VOM installed)
Each of the five VOM modes have factory presets, that when initiated by a VOM contact
closure, will accomplish five predefined operations (listed below). Any of the five
sequences may be user-redefined by changing the factory presets at the unit mounted
Human Interface or through Tracer.
Ventilation Override Mode A - (Unit Off)
Supply Fan - Off
Inlet Vanes / VFD - Closed/0%
Return Fan VFD - Min
Return Fan/Exhaust Damper - Off/Closed (if equipped)
OA Dampers - Closed
Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output
at 0%.
Occupied/Unoccupied output-Deenergized
VO Relay - Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode B - (Pressurize)
Supply Fan - On
Inlet Vanes / VFD - Open/100%
Return Fan VFD - Min
Return Fan/Exhaust Damper - Off/Closed (if equipped)
OA Dampers - Open
Heat - All heat stages Off (staged gas & elec.), Hydronic heat & Mod Gas Heat output at
0%.
Occupied/Unoccupied output-Energized
VO Relay-Energized
VCM Preheater State - Off (with VCM installed)
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.