72 RT-SVP04F-EN
System Programming SETUP
GBAS 0 - 5 VDC Module I/O Assignments Used with: All Units when GBAS 0-
5 VDC is installed.
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
GBAS (0 - 5 VDC) Analog Input 1 Assignment Used with: All Units when GBAS 0-
5 VDC is installed.
Factory Presets: Not Assigned
Possible Values: Not Assigned,
Unoccupied Zone Cooling SETPOINT
Occupied Zone Heating SETPOINT
Unoccupied Zone Heating SETPOINT
Space Static Pressure SETPOINT, SA
Static Pressure SETPOINT, Min OA
Flow SETPOINT, Morning Warmup
SETPOINT, Econ Dry Bulb Enable
SETPOINT, Minimum Position
SETPOINT, Occupied Dehumid
SETPOINT, Unoccupied Dehumid
SETPOINT, Supply Air Reheat
SETPOINT, Occupied Humidification
SETPOINT, Unoccupied
Humidification SETPOINT
NOT ASSIGNED
1. Press the + or - key until the proper selection is displayed for the
number 1 assignment.
2. Press the ENTER key to confirm this choice. Only one input
definition can be assigned to each input and they can not be
duplicated.
3. Press the NEXT key to advance to the number 2 input assignment
screen and repeat steps 1 & 2. Follow these steps for input
assignments 3 and 4.
4. Press the NEXT key until the following screen is displayed.
GBAS (0 - 5 VDC) Output 1 Alarm Assignments Used With: All Units when GBAS 0-
5VDC is installed
Factory Presets:
Output 1 = Dirty Filters
Output 2 = Compressor Trip
Compressor Trip - Ckt 1
Compressor Trip - Ckt 2
Low Pressure Control Open
Low Pressure Control Open - Ckt 1
Low Pressure Control Open - Ckt 2
Comp Contactor Fail
Comp Contactor Fail - Ckt 1
Comp Contactor Fail - Ckt 2
Output 3 = Heat Fail
Output 4 = Supply Fan Failure
Output 5 = Any Active Diagnostic
Possible Values: Refer to the list of
active diagnostics that can be
assigned to each of the five (5)
output definitions in the
"Diagnostics Menu" section.
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
2. Press the + or - key until the proper selection is displayed for the
number 1 assignment. + (Plus) key will assign ALL Diagnostics and -
(Minus) key will allow diagnostic selection.
3. Press the ENTER key to confirm this choice. If (Yes) was assigned to
the Output assignment, the output 2 assignment screen will be
displayed. Repeat step 1 for each of the remaining
4 Outputs. If (NO) was assigned, only one output assignment can be
assigned to each output assignment and they can not be duplicated.
Once the output diagnostics have been defined, press the NEXT key to
advance to the number 2 output assignment screen and repeat steps
1 & 2.
Note: Assigning "Yes" to a GBAS output definition means that if the
assigned diagnostic is present, the output assigned to it will be
energized.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
This screen is displayed when GBAS 0-10 VDC Module is installed