80 RT-SVP04F-EN
System Programming SETUP
Temperature Calibration Offset For Used With: All Units when Gas,
Electric, or Hydronic Heat is installed
Factory Presets: 0.0 F
Possible Values: Plus or Minus 5.0
F
Heat Module Aux Temp Input 0.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Temperature Calibration Offset For Used With: All Units when
comparative enthalpy is installed
Factory Presets: 0.0 F
Possible Values: Plus or Minus 5.0
F
ECEM Return Air Temperature Input 0.0 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
Device Characteristic Setup Definitions Used with: All Units
Press ENTER to review or Adjust
1. Pressing the NEXT key will bypass this section.
Actuator Setup OA Damper Used With: All Units when an
economizer is installed
Factory Presets: 30 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 30 Sec
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup OA Damper Used With: All Units when an
economizer is installed
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts
DC
Min Voltage 2.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup OA Damper Used With: All Units when an
economizer is installed
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts
DC
Max Voltage 10.0 VDC
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.