RT-SVP04F-EN 65
System Programming SETUP
Maximum OA Flow at Design Conditions XXX CCFM Used With: All units with OA
Normalization: Return Fan and units
with Fresh Air Measurement w/DCV
(VCM) installed.
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the + (Plus) key while viewing any screen to add that
screen to the custom menu. Refer to the custom menu for the
creation and maintenance of customized menus.
4. Press the NEXT key until the following screen is displayed.
(if applicable)
OA Flow Calibration Data Used With: All units with Fresh Air
Measurement w/DCV (VCM)
installed.
Altitude: 0 Ft.
1. Press the + or - key until the proper value is displayed
2. Press the ENTER key to confirm this choice
3. Press the NEXT key until the following screen is displayed
OA Flow Calibration Data Altitude Values & Associated Data
ENGLISH SI ENUM CORR FACTOR
0 ft 0 m 1.00
500 ft 150 m 0.99
1000 ft 300 m 0.98
1500 ft 450 m 0.97
2000 ft 600 m 0.97
2500 ft 750 m 0.96
3000 ft 900 m 0.95
3500 ft 1050 m 0.94
4000 ft 1200 m 0.93
4500 ft 1350 m 0.92
ENGLISH SI ENUM CORR FACTOR
5000 ft 1500 m 0.91
5500 ft 1650 m 0.91
6000 ft 1800 m 0.90
6500 ft 2000 m 0.89
7000 ft 2150 m 0.88
7500 ft 2300 m 0.87
8000 ft 2450 m 0.86
8500 ft 2600 m 0.85
9000 ft 2750 m 0.85
9500 ft 2900 m 0.84
10000 ft 3050 m 0.83