60 RT-SVP04F-EN
System Programming SETUP
Economizer Control Functions Submenu Used with: All Units when an
economizer is installed.
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Economizer Cntrl Enable Type: REFERENCE Used With: All Units when an
economizer is installed
Factory Presets: REFERENCE
Possible Values: REFERENCE,
DRYBULB
When Comparative Enthalpy Not Available
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Unocc Air Economizer Function: ENABLED Used With: All Units when an
economizer is installed
Factory Presets: ENABLED
Possible Values: ENABLED,
DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
Head Pressure Ctrl Setup Submenu Used with: Rooftops and Air
Handlers when DX cooling is
installed
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Sump Drain Valve Relay Control is: DRAIN Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: DRAIN
Possible Values: HOLD, DRAIN
During Unit Power Loss Conditions
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Sump Purge Interval Timer: 3 Hrs. Used With: All IntelliPak II units
with water-cooled condensers
installed.
Factory Preset: Interval Timer: 3
hours.
Possible Values: Interval Timer: 1-
12 hours; Duration Timer: 30-60
sec., default is 30 sec.
Sump Purge Duration Timer: 60 Sec.
Note: Sump Purge Duration Timer: only shown if Interval Timer
not DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)