RT-SVP04F-EN 61
System Programming SETUP
Sump Water Heater Setpoint: 38°F Used With: All IntelliPak II units
with water-cooled condensers and
sump heat installed.
Factory Preset: 38 F
Possible Values: 38-43 F
Low Sump Temp Activates Heater Output
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Cond Temp Control Band Used With: All Rooftop Units and
Air handlers when DX Cooling is
installed.
Factory Presets:
Upper: 120 F,
Lower: 80 F
Possible Values: Lower: 70 F to 90
F, Upper: 110 F to 130 F
Lower Limit: 80 F Upper Limit: 120 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Cond Temp Control Band Used With: All Rooftop Units and
Air handlers when DX Cooling is
installed.
Factory Presets:
10 F
Possible Values: 0 to 20 F
Temporary Low Limit Suppression: 10 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Cond Temp Used With: All Rooftop Units and
Air handlers when DX Cooling is
installed.
Factory Presets:
105 F
Possible Values: 95 to 115 F
Efficiency Check Point: 105 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Cond Temp Used With: All Rooftop Units and
Air handlers when DX Cooling and
low ambient dampers are installed.
Factory Presets:
90 F
Possible Values: 80 F to 100 F
Low Ambient Control Point: 90 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: All low ambient dampers
control to this condensing
temperature
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.