RT-SVP04F-EN 31
System Operating Status
Disable or Lockout Sources
Disabled By Compressor Protection (Compressor proving input did not close)
Disabled By Contactor Failure (Compressor proving input stuck closed)
Disabled By Low Pressure Cutout (Low pressure cutout input to MCM)
Disabled By Bad Cond Temp Sensor (Temp Sensor is out of -40 F to 200 F range)
Disabled By Demand Limit (From GBAS or BAS/Network)
Disabled By Frost Protection (Leaving evap temp sensor colder than coil frost
temp setpoint (25 F to 35 F)
Disabled By BAS/Network Lockout
Disabled By Minimum Off Time (3 minutes)
Disabled By Low Ambient Lockout (setpoint range -20 F to 80 F)
Disabled By Ventilation Override (VOM input A-E or BAS/Network)
Disabled By LPC Delay (3 minutes)
Disabled By Water Flow Status
Disabled By Cond Coil Purge Request
Disabled By Sump Temp Sensor Fail
Disabled By Low Refrig Charge (Evap temp limit setpoint (24-45 F) has been
exceeded for 10 minutes
Disabled By Evap Temp Sensor Fail
Disabled By Sump Min Level Sensor Fail
Disabled By Sump Pump Failure
Disabled By Sump Min Level Control
* These entries apply to the following 4 screens.
Note: If a compressor output is
disabled or locked, these
lockout sources will be
found in the bottom field for
IntelliPak I, or in the second
field for IntelliPak II.
Circuit 1 Evap Diff: 5.0
Enter Evap: 48.5 Leave Evap: 53.5
Used With: All Rooftop Units and
Air Handlers when DX cooling is
installed.
Possible Values: Evap Diff. = 0.0
to 200.0 ºF, Enter Evap= -40.0 to
200.0 ºF, Leave Evap: -40 to 200.0
ºF
1. Press the NEXT key until the following screen is displayed. (if
applicable)
Note: "Evap Diff" and associated value not displayed on inactive
circuit or for first ten minutes of circuit operation or if HGBP is
installed.
Note: "Enter Evap" and associated value not displayed if HGBP is
installed
1. Press the NEXT key until the following screen is displayed.
Circuit 1
Saturated Condensing Temp: 100.0
Used With: All Rooftops or Air
Handlers with DX Cooling.
Possible Values: Saturated
Condensing Temp= -40.0 to 200.0
ºF
1. Press the NEXT key until the following screen is displayed.