System Operating Status
Circuit 2 Evap Diff: 12.0
Enter Evap: 40.0 Leave Evap: 52.0
Used With: All Rooftops or Air
Handlers with DX Cooling.
Possible Values: Evap Diff. = 0.0
to 200.0 ºF, Enter Evap= -40.0 to
200.0 ºF, Leave Evap: 40.0 to 200.0
ºF
1. Press the NEXT key until the following screen is displayed.
Note: "Evap Diff" and associated value not displayed on inactive
circuit or for first ten minutes of circuit operation or if HGBP is
installed.
Note: "Enter Evap" and associated value not displayed if HGBP is
installed
1. Press the NEXT key until the following screen is displayed.
Circuit 2
Saturated Condensing Temp: 97.0
Used With: All Rooftops or Air
Handlers with DX Cooling.
Possible Values: Saturated
Condensing Temp= -40.0 to 200.0
ºF
1. Press the NEXT key until the following screen is displayed.
Circuit 1 Cond Fan Staging Used With: All units except Air
Handlers.
Possible Values: K1= ON, OFF;
K2= ON, OFF; Cond Fan Staging=
OFF, Stage 1, Stage 2, Stage 3,
Stage 4
K1: ON K2: ON Stage 4
1. Press the NEXT key until the following screen is displayed.
Note: K2 status not displayed and maximum stage is 1 on water-
cooled condenser units.
Circuit 2 Cond Fan Staging Used With: All units except Air
Handlers.
Possible Values: K5= ON, OFF;
K6= ON, OFF; Cond Fan Staging=
OFF, Stage 1, Stage 2, Stage 3,
Stage 4
K5: ON K6: ON Stage 4
Note: K6 not displayed and maximum stage is 1 on water-cooled
condenser units.
1. Press the NEXT key until the following screen is displayed.
Condenser Fan Speed: Used With: All IntelliPak II units
configured with low ambient control
or water-cooled condensers
Possible Values: Circuit 1= 0 to
100%; Circuit 2= 0 to 100%
Circuit 1: 100% Circuit 2: 100%
1. Press the NEXT key until the following screen is displayed.
Condenser Sump Water Temp: 73.1°F Used With: All IntelliPak II units
with water-cooled condensers
installed. Sump Heater Relay is
displayed if sump heater installed
Possible Values: Sump Water
Temp: 0.0 to 200.0 F; Sump Heater
Relay: ON, OFF
Condenser Sump Heater Relay: OFF
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)