RT-SVP04F-EN 59
System Programming SETUP
Supply Air Temp Zone Reset For Heating: Used With: All Units when Zone
Heating reset is selected.
Factory Presets:
Start Temp: 65 F, End Temp: 68 F
Possible Values:
Start: 50 - 89 F
End: 51 - 90 F
Start Temp: 65 F End Temp: 68 F
1. Press the NEXT key until the following screen is displayed.
Supply Air Temp Outside Air
Reset For Heating: Used With: All Units when Outside
Air Heating Reset is selected.
Factory Presets:
Start Temp: 10 F, End Temp: 60 F
Possible Values:
Start: 0 - 94 F
End: 1 - 95 F
Start Temp: 10 F End Temp: 60 F
1. Press the NEXT key until the following screen is displayed.
Supply Air Temp ZONE Reset For Heating: Used With: All Units when Zone
Heating is selected.
Factory Presets:10F
Possible Values: 10 - 90 F
Maximum Amount of Reset Applied: 10 F
1. Press the NEXT key until the following screen is displayed.
Supply Air Temp OA Reset For Heating: Used With: All Units when Outside
Air Heating is selected.
Factory Presets:10F
Possible Values: 10 - 90 F
Maximum Amount of Reset Applied: 10 F
1. Press the NEXT key until the following screen is displayed.
VAV Box Max Stroke Time: 6 Min Used With: All Units
Factory Presets: 6 Min
Possible Values: 0 to 100%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Max Occupied IGV/VFD Command: 100% Used With: All Units when IGV/VFD
is installed
Factory Presets: 100%
Possible Values: 0 to 100%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.