58 RT-SVP04F-EN
System Programming SETUP
Supply Air Temp Zone Reset For Cooling: Used With: All Units when Zone
Cooling Reset is selected.
Factory Presets:
StartTemp= 78F
EndTemp= 75F
Possible Values:
Start: 67 - 81 F
End: 60 - 80 FF
Start Temp: 72 F End Temp: 69 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Supply Air Temp Outside Air
Reset For Cooling: Used With: All Units when Outside
Air Reset is selected.
Factory Presets:
StartTemp= 90F
EndTemp= 70F
Possible Values:
Start: 46 - 125 F
End: 45 - 124 F
Start Temp: 90 F End Temp: 70 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Supply Air Temp Zone
Reset For Cooling: Used With: All Units when Zone
Reset is selected.
Factory Presets: 5 F
Possible Values:
0 - 20 F
Maximum Amount of Reset Applied: 5 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Supply Air Temp Outside Air
Reset For Cooling: Used With: All Units when Outside
Air Cooling Reset is selected.
Factory Presets:
5 F
Possible Values:
0 - 20 F
Maximum Amount of Reset Applied: 5 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)