EasyManua.ls Logo

Trane IntelliPak I - Page 57

Trane IntelliPak I
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RT-SVP04F-EN 57
System Programming SETUP
Evap Temperature Limit. Shut Off Circuit
if (Leaving - Entering) Exceeds: 35ºF
Used With: All Units
Factory Preset: 35º F
Possible Values: 25-40º F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Note: On units with Dehumidification installed a non-adjustable
Evap Temperature Limit of 40 F is used for the Reheat Circuit
only.
Coil Frost Cutout Temperature. Shut off
Compressors If Evap Temp Is Below: 30 F
Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice. Factory Preset: 30 F
3. Press the NEXT key until the following screen is displayed. Possible Values: 25 F to 35 F
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
VAV Control Functions Submenu
Press ENTER to Review or Adjust
Used With: All Units
1. Press the NEXT key until the following screen is displayed.
Supply Air Temp Reset Type:
Cooling: NONE
Used With: Rooftops and Air
Handlers when no cooling is installed
Possible Values: Cool: NONE,
ZONE, OA
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Supply Air Temp Reset type: Used With: All Units when
Hydronic, Electric, or Modulating
Gas Heat installed
Possible Values: Cool/Heat: NONE,
ZONE, OA
Cooling: NONE Heating: NONE
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)

Table of Contents