56 RT-SVP04F-EN
System Programming SETUP
Occ Humidification Function: DISABLED
Unocc Humidification Function: DISABLED
Used With: All units with
Humidification option enabled.
Factory Presets: ENABLED
Possible Values: ENABLED,
DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
VCM Preheater Output Control: ENABLED
Activate If Preheat Temp Below SETPOINT
Used With: All Units when VCM is
installed
Factory Preset: DISABLED
Possible Values: ENABLED,
DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Demand Limit Definition:
Cooling: None
Used With: All Rooftop units (or Air
Handler with DX Cooling) with GBAS
or LCI or BCI installed
Factory Presets: NONE
Possible Values: Cooling: 25, 50,
75, 100%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: NONE=No Limit to Cooling;
100% = 100% of Cooling
Capacity is Limited
Demand Limit Definition:
Cooling: None ......................................Heating: None
Used With: All units with Gas,
Electric, or Hydronic heat with GBAS
or LCI or BCI installed
Factory Presets: None
Possible Values: Cooling: 25, 50,
75, 100%
Heating: 50% or 100%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: NONE=No Limit to Cooling;
100% = 100% of Cooling
Capacity is Limited
Compressor Lead/Lag Function: ENABLED
Vary Staging Order To Distribute Runtime
Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed
Factory Preset: ENABLED
Possible Values: ENABLED,
DISABLED = Stage Comp(s) Up/
Down In Fixed Sequence
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.