RT-SVP04F-EN 55
System Programming SETUP
Morning Warmup Function: ENABLED
Morning Warmup Type: FULL CAPACITY
Used With: All Units when Gas,
Electric, or Hydronic Heat is
installed.
Factory Presets: Function:
ENABLED, MWU Type: Full
Capacity
Possible Values: Function:
ENABLED, DISABLED
MWU Type: FULL CAPACITY,
CYCLING CAPCITY
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Supply Air Tempering Function: ENABLED
Warm Up Outside Air Used For Ventilation
Used With: All Units when
Modulating Gas, Electric or Hydronic
Heat is installed
Factory Preset: ENABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: Possible Values: ENABLED,
DISABLED* (Note: Supply
Air Tempering is not used
with staged gas heat)
Unocc Mech Cooling Function: ENABLED Used With: All Rooftop Units and
Air Handler Units when DX Cooling is
installed or Air Handler with chilled
water installed.
Factory Preset: ENABLED
Possible Values: Cooling:
ENABLED, DISABLED
OR
Unocc Mech Cooling Function: ENABLED
Unocc Heating Function: ENABLED
Used With: All Units when Gas,
Electric, Hydronic, or External Heat
is installed
Factory Presets: Cooling &
Heating: ENABLED
Possible Values: Cooling &
Heating: ENABLED, DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Occupied Dehumid Function: ENABLED
Unoccupied Dehumid Function: ENABLED
Used With: All units with
Dehumidification installed.
Possible Values: ENABLED,
DISABLED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).