RT-SVP04F-EN 71
System Programming SETUP
Ventilation Override Definition Mode A Used With: All Units when VOM is
installed and OA preheater function
is enabled
Factory Presets: Refer to
Definitions
Possible Values: OFF, IN CONTROL
VCM Preheater State IN CONTROL
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Ventilation Override Definition Mode A Used With: All Units when VOM is
installed
Factory Presets: Refer to
Definitions
Possible Values: ENERGIZED/
DEENERGIZED
Ventilation Override Relay ENERGIZED
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Ventilation Override Definition Mode A Used With: All Units
Factory Presets: Not Locked
Possible Values: Not Locked,
Locked
Enter Password to Lock Definition:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Note: After locking a MODE (by entering the password), the display
for that MODE becomes "Reporting" only and the definition can not be
changed unless the Ventilation Override Module is replaced. If the
password was entered, pressing the NEXT key will scroll through the
previous screens to confirm the selected choices for each mode as
follows:
Ventilation Override Mode A Is Locked Used With: All Units when VO mode
is locked
Factory Presets: Refer to the
Definitions
Possible Values: N/A
Supply Fan
Key functions for the locked VOM displays are as follows:
The ENTER, +, and - keys are disabled.
The PREVIOUS and NEXT keys will advance to the previous and next
screens respectively. After all of the VOM modes have been viewed or
modified, the following screen will be displayed.
Ventilation Override Mode B Used With: All Units
Factory Presets: Refer to the
Definitions
Possible Values: ON, OFF
Supply Fan
1. Follow the preceding steps used to program MODE "A" to program
MODE B", "C", "D", and "E" if modifications are needed. After all of the
Ventilation Override Definitions have been programmed, pressing the
NEXT key will advance to the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.